25th Annual Report, Volume I, Section 4.24, Closed Loop Cooling

4.24.1 Overview and Previous Activities

The purpose of the section is to describe the DCISC’s review of the Environmental Protection Agency’s (implemented by the California State Water Resources Control Board) proposed new rules on requiring closed loop cooling, i.e., cooling towers, on power plants with once-through cooling. The DCISC reviewed the following during the previous reporting period:

The DCISC has found a number of potential nuclear safety issues with the use of cooling towers at DCPP. The DCISC intends to follow this issue over the next year or more and to review the operational safety implications of any proposal that would replace Once Through Cooling with a cooling towers or different technologies.

4.24.2 Current Period Activities

During the current period, the DCISC reviewed the following closed loop cooling items:

State Water Resources Board (Volume II, Exhibit D.5, Section 3.3)

The State of California regulates the use of Once-Through-Cooling (OTC) through the State Water Resources Control Board (SWRCB). OTC is a method of cooling that draws water from a large body (e.g. the Pacific Ocean) and pumps it through heat exchangers where it absorbs the heat from other systems and is returned to and gives up its heat to the same body from which it was initially drawn. In DCPP’s case, the station draws water from the Pacific Ocean, pumps it through the main condenser in which it condenses steam (that had been used to spin the turbine generators, as well as a variety of other much smaller heat exchangers, and is now “spent”) into water so that the water can be pumped back to the steam generators in a closed loop. In the steam generators, this same water is reheated to steam by the reactor coolant system, which is a separate closed loop. The water coming from the Pacific Ocean returns in a warmed condition back to the Pacific, where it gives up its heat to the Pacific. The OTC system impacts fish and other living organisms that are drawn into the intake or that live in the warmed ocean water.

California adopted a new OTC-Policy in October 2010, which requires users of OTC to examine alternative cooling methods to reduce or eliminate the environmental effects the OTC system is having on the Pacific. The state policy acknowledges the special contributions that nuclear plants make to the environment and to the electric generation system in that the plants are not producers of greenhouse gases and they provide a reliable base load of electric generation. Nevertheless, the policy requires that each nuclear generating station evaluate alternatives to OTC by comparing the alternatives to OTC against current OTC from the standpoints of environmental protection, safety, and economics, which includes reliability and availability of electric generation. The SWRCB will review the results of the evaluations, and it has established a special Nuclear Review Committee to oversee the special studies being performed by California’s nuclear utilities, who have engaged third-party contractors to perform these studies.

On July 3, 2014 the DCISC received a copy of Bechtel’s draft Addendum on the use of salt water cooling towers south of DCPP and on August 6, 2014, DCISC posted its draft evaluation of Bechtel’s report. On August 8, 2014, DCISD held a public meeting to review comments received from the Public. The comment period was then extended further, and on October 14, 2014 the DCISC approved its “Preliminary Evaluation of Safety Issues for Bechtel’s Addendum to the Independent Third-Party Final Technologies Assessment for the Alternative Cooling Technologies of Modification to the Existing Once-Through Cooling System for the Diablo Canyon Power Plant Addressing the Installation of Saltwater Cooling Towers in the South Parking Lot.” DCISC’s Preliminary Evaluation was provided for the SWRCB’s consideration at its meeting on November 18, 2014. The DCISC also specifically noted in its report that it would continue to study the safety implications of alternatives to once-through cooling, recognizing that additional information might be developed concerning these issues by Bechtel and/or PG&E. Therefore, it was (and is) possible that DCISC might modify its own evaluations of these open issues.

Some of the major issues noted by DCISC’s review are as follows:

In summary, the DCISC’s October 14, 2014 report contained a number of Conclusions and Recommendations: (The Conclusions are listed in their respective section at the end of this topic of the Fact-finding Report. DCISC’s Recommendations are listed immediately below. They are included as documentation of DCISC’s Recommendations in its October 17, 2014 Report to the California State Water Resources Control Board and, therefore, do not require a Response or action by PG&E at this time. Therefore, these Recommendations will not be included in the “Recommendations” Section of this Fact-finding Report.)

DCISC Recommendation 1: An evaluation should be performed to understand the impact of southern-sited cooling towers on plant security and emergency response capabilities.

DCISC Recommendation 2: Additional review/analysis should be performed to provide an estimate of how extensive an NRC review might be necessary concerning the cooling tower options. Such an effort should incorporate NRC staff inputs.

DCISC Recommendation 3: A probabilistic risk assessment analysis should be made to quantify the impact of cooling towers on the risk of transients and accidents and any change to the margins of safety.

DCISC Recommendation 4: Simulation of rates of salt deposition from salt-water cooling towers, using available modeling tools, should be performed to assess the increase in salt deposition rates that would occur if salt water, rather than fresh water, were used in cooling towers at the site, and these simulations should be used to assess potential impacts on plant safety systems and plant reliability, to inform the decision on whether fresh water or salt water should be used.

DCISC’s October 14, 2014 report also reflected on other earlier major DCPP construction projects that have affected plant access, most notably the major post 9/11 security upgrades, where all of the plant security modifications were assessed for their safety impacts, where temporary security measures were implemented, and where the modifications were examined with respect to their effect on operations and maintenance.

In addition, DCISC’s October 14, 2014 report to California SWRCB revisited DCISC’s earlier review and assessment of Bechtel’s initial study of closed cooling tower options as well as DCISC’s conclusions regarding that Bechtel study, as contained in DCISC’s May 25/26, 2014 Fact-finding Report. Since DCISC’s specific four major conclusions for this earlier review have already been documented and discussed in DCISC’s May 2014 Fact-finding Report, they will not be duplicated in this December 2014 Fact-finding Report. However, this December 2014 Fact-finding notes that those four major conclusions remain valid.

The DCISC Fact-finding Team also briefly toured the 85-foot level of the Turbine Building to inspect potential flooding hazards associated with the turbine condensers located at this elevation. This “85-foot” level is actually “ground level” which is 85 feet above the Pacific Ocean. With cooling towers, the large-diameter circulating water piping, water boxes, and condenser tubes would operate at higher pressure, with their water supply located above the condensers rather than below. The key concerns for flooding involve the emergency diesel generators and safety related electrical switchgear that are at the same elevation and adjacent to the condensers. This equipment is housed in rooms separate from the condenser area, so the primary flooding risks would come from the doors that connect these areas. Any large-scale flooding from the condensers would most likely flow out exits from the west side of the turbine building, but a detailed flooding assessment will be needed to confirm this.

To reduce the size of the cooling towers in order to allow them to fit within the smaller footprint available to the south of the plant, and to reduce the cost of the cooling towers, the cooling towers being considered are sized to operate with higher circulating water temperature than the earlier design that was considered. This results in a somewhat higher condenser back pressure and somewhat lower output from the plant turbines. However, the turbine vendor has indicated that these low pressure turbines can operate reliably at a higher condenser pressure of 4 to 5 inches Hg.

The impacts of southern siting of cooling towers on plant access during construction, and the increased salt deposition on plant equipment from use of salt-water cooling, would both have the potential for more negative safety impacts than would northern siting and use of reclaimed and desalinated water. Conversely, operating with higher cooling temperatures would have minimal safety impact.

The logistics for maintaining effective plant access for normal operations and emergency response, as well as meeting requirements for physical security during the six-year cooling tower construction period prior to the dual-unit outage, will be substantially more complex for the southern siting option.

Installation of cooling water ducts in the protected area will impact operability and require design changes to the emergency diesel generator fuel tanks and the auxiliary saltwater system, and will require analysis for new flooding risks for safety-related equipment (emergency diesel generators and switch gear) located in the 85-foot elevation of the turbine building. The 85-foot elevation is “ground level’ for the Turbine Building because the plant is on a cliff that is 85 feet above the Pacific Ocean. Southern siting would also require redesign and replacement of the underground Auxiliary Saltwater System piping, which, when modified by DCPP in the past, has required a NRC License Amendment Request (LAR). Combined with other safety related impacts related to emergency response, fire protection, and security, implementation of closed cooling with southern siting will require NRC review and appears likely to trigger a requirement for a NRC LAR, which would lead to a potentially lengthy NRC review.

The design of the proposed temporary emergency diesel generators will require very careful review to assure that safety can be maintained.

It is unlikely that the existing ASW lines, which are integrated into the existing circulating water system underground concrete duct structure, could be maintained. Instead, temporary rerouting of ASW lines to maintain spent fuel pool cooling, followed by replacement, will be needed. This would continue to maintain safety system cooling but would add some adverse risk to plant operational safety.

The use of salt water cooling towers could result in an increase in the rate of deposition of salt on DCPP plant equipment during the 10.1% of the year that wind blows from the east-south-east and the 23.3% of the year when wind speeds are very low, compared to the rate currently experienced. Higher salt deposition rates have the potential to create negative impacts on some safety-related systems, in particular Emergency Diesel Generators, and ventilation systems for the Auxiliary Building, Control Room, and Fuel Handling Building. Higher salt deposition rates may also reduce the reliability of outdoor high voltage systems that plan a major role in plant safety, and increase the frequency of loss of off-site power (LOOP) events. These higher salt deposition rates could also produce negative impacts on the long-term safety of the spent fuel casks in the Independent Spent Fuel Storage Installation (ISFSI), although these effects should be much less because of the longer distance from the ocean to the ISFSI.

Operation of the DCPP condensers at a higher pressure of 4 to 5 inches Hg is unlikely to affect plant safety significantly.

Salt Deposition on Equipment at DCPP (Volume II, Exhibit D.8, Section 3.4)

DCPP shared data for the following areas of the plant:

Plant Area Salt Contamination Level (ESSD)∗
230 kV Switchyard Buses Light
230 kV Switchyard Insulators Medium to Extra Heavy
230 kV Transformer Yard Insulators Light
500 kV Transformer Yard H0 Bushing (Unit 1) Heavy
500 kV Transformer Yard H1 Bushing (Unit 1) Medium to Extra Heavy
500 kV Transformer Yard H0 Bushing (Unit 2) Heavy
500 kV Transformer Yard H1 Bushing (Unit 2) Medium to Heavy

∗Where
Light = 0.03–0.08 mg/cm2 (Equivalent Salt Deposit Density)
Medium = 0.08–0.25
Heavy = 0.25–0.6
Extra Heavy = > 0.6

These data were measured in the February—March, 2015 timeframe. The salt came from the Pacific Ocean spray, primarily from water exiting the plant discharge cascading down the discharge outfall. The level of deposition depended on the distance from the ocean and the exposure to the ocean.

The frequency and level of cleaning were directly proportional to the salt contamination level and other contaminants such as dirt and dust.

4.24.3 Conclusions and Recommendations

Conclusions:
The DCISC has found a number of potential nuclear safety issues with the use of cooling towers at DCPP. The DCISC intends to follow this issue over the next year or more and to review the operational safety implications of any proposal that would replace Once Through Cooling with cooling towers or different technologies.
Being an ocean-sited power plant, DCPP is susceptible to salt contamination from ocean spray. DCPP measurements of contamination levels on outdoor components showed what one would expect: contamination levels were directly proportional to the closeness and exposure to the ocean. Contamination levels ranged from Light to Extra Heavy.
Recommendations:
None

Appendix 1

Diablo Canyon Independent Safety Committee’s Evaluation of Safety Issues for “Independent Third Party Final Technologies Assessment for the Alternative Cooling Technologies or Modifications to the Existing Once-Through Cooling System for the Diablo Canyon Power Plant’“

5 September 2013

Concurred in by the Three Members of the DCISC at the DCISC Public Meeting on 4 September 2013

Background: The request from the SWRCB “Review Committee”

In early 2011, the California State Water Resources Control Board appointed a special committee, a “Review Committee to Oversee Special Studies for the Nuclear-Fueled Power Plants Using Once-through Cooling” (the “Review Committee”) to assist it in evaluating various technical options that might be used to replace or reduce the environmental impacts of once-through cooling (OTC) at the two nuclear power plants along California’s Pacific coast, Diablo Canyon and San Onofre. To discharge its charter, the Review Committee requested the two companies then operating those nuclear power plants, Pacific Gas and Electric Company and Southern California Edison Company, to contract for a technical evaluation.

Bechtel Power Corporation was selected as the contractor, and its technical work is the subject of the evaluation here. Specifically, Bechtel published a preliminary study in November 2012 (Reference 1), and then in August 2013 published a follow-up technical study (Reference 2) that extends their earlier work in more detail. The current study remains at the conceptual level but contains sufficient details to reach some high-level conclusions on the nuclear-reactor-safety issues. The level of design detail remains insufficient to assess the impact of the potential design changes on the plant reliability and frequency of trips and forced outages, and to assess potential safety impacts that could occur during or after construction of the modified cooling systems.

The original scope for Bechtel was to provide information and analysis related to both Diablo Canyon and San Onofre. However, in summer 2013 Southern California Edison announced that San Onofre would be permanently closed, after which Bechtel’s work has concentrated only on Diablo Canyon. The scope of the DCISC’s evaluation here is also related only to the Diablo Canyon Power Plant (DCPP).

During its meeting on 13 August 2013 in Sacramento, the Review Committee made a request of the DCISC. The specific request was that the DCISC provide a technical evaluation of the nuclear-reactor-safety issues associated with seven alternative cooling technologies or modifications to the existing once-through cooling system for DCPP. The request asked if the DCISC could provide its evaluation by 5 September 2013, which represented a very tight schedule. One of the DCISC’s three members (Dr. Budnitz) attended the 13 August meeting, at which he agreed that the DCISC could and would do such an evaluation and would try to meet this schedule. The DCISC’s evaluation has concentrated on Bechtel’s second report (Reference 2), but has also relied in part on Bechtel’s earlier work in Reference 1 as a source of important technical information.

Additional information related to the evaluation

  1. Light water power reactors, like the two units at Diablo Canyon, produce large amounts of “waste heat” that must be discharged to the environment. During normal operation, the waste heat is discharged to the Pacific Ocean from the Condenser via the Condenser Circulating Water System. During off-normal or emergency conditions or when one or both reactors are shut down, residual decay heat can be ultimately discharged to the Pacific Ocean via a separate safety-related Auxiliary Saltwater (ASW) System termed the “ultimate heat sink” (UHS), and we will use that term here.
  2. Today, Diablo Canyon’s normal heat discharge to the adjacent Pacific Ocean uses the specific technology called once-through cooling (OTC), in which cool ocean water is pumped into the plant, warmed up about 20 degrees Fahrenheit, and returned to the ocean. The current OTC approach inevitably produces environmental impacts on the nearby ocean, and the motivation for the current review of OTC is a desire to decrease these impacts by a change in cooling technology. While each of the seven alternatives being evaluated by Bechtel has a different mix of environmental impacts, and although the waste heat must go “somewhere in the environment,” this set of environmental-impact issues is beyond the scope of DCISC’s evaluation here.
  3. The SWRCB is currently considering a new regulatory position that would require Diablo Canyon to replace its current OTC system with a system that would produce smaller environmental impacts on certain aspects of the ocean environment.
  4. A paraphrasing of Bechtel’s initial scope is that Bechtel was asked to identify a very large range of technically feasible cooling alternatives that might be deployed at Diablo Canyon. It discharged that assignment in its first report (November 2012, Reference 1).
  5. The SWRCB Review Committee reviewed Bechtel’s report, and based on criteria that are beyond our scope here, the Review Committee directed Bechtel to narrow the options to seven that were to be evaluated further. In the next phase of Bechtel’s work (Phase 2), more detailed conceptual designs and engineering analyses were completed for each of these seven options, and Bechtel also performed a review of the relevant nuclear-reactor-safety issues for each. A cost study is also part of Bechtel’s Phase 2 work, but evaluating it is outside of the DCISC’s scope.
  1. The seven technologies are as follows:
  1. Providing reliable and effective cooling is an important aspect of the overall safety of a nuclear power plant’s design, and, as noted above,the DCISC’s concern here is to evaluate the implications of a change in cooling technology on the overall nuclear-reactor safety at Diablo Canyon.

Bechtel’s safety assessment and conclusions

As noted above, in Bechtel’s recent report (Reference 2) the Bechtel team has performed an assessment of the nuclear-reactor safety of each of the seven alternative cooling options that might replace OTC at Diablo Canyon. Bechtel based its assessment on a set of criteria specified by the Review Committee. This set of criteria, called in the Bechtel report “Criterion 10,” covers eight “areas of NRC interest,” against each of which the assessment was performed. The NRC regulation 10 CFR 50.59 (Reference. 3) is a major basis for these criteria. Diablo Canyon’s Final Safety Analysis Report Update (Reference. 4) is cited by Bechtel as one of the major regulatory documents used by the NRC and the plant to document the plant’s safety analyses.

The eight areas are:

  1. Seismic issues
  2. Operability
  3. Transient analyses
  4. Nuclear fuel (accident analyses)
  5. Single failures
  6. Hydraulic design
  7. probabilistic risk assessment
  8. Instrumentation controls and alarms

The Bechtel report states,“Criterion 10 is a feasibility assessment based on regulatory requirements established by 10 CFR 50.59 to determine whether NRC approval of the alternative technology is required.”

For each of the seven alternative UHS options, Bechtel has concluded as follows (Reference. 2, Section 1.5, “Conclusions”):

“Based on the results of the feasibility assessment and when more detailed engineering information becomes available, the anticipated responses to the following eight 10 CFR 50.59 criteria questions for each of the proposed modifications would be NO:”

  1. Result in more than a minimal increase in the frequency of occurrence of an accident previously evaluated in the FSARU [Final Safety Analysis Report Update]?
  2. Result in more than a minimal increase in the likelihood of occurrence of a malfunction of an SSC [structure, system, or component] important to safety previously evaluated in the FSARU?
  3. Result in more than a minimal increase in the consequences of an accident previously evaluated in the FSARU?
  4. Result in more than a minimal increase in the consequences of a malfunction of an SSC important to safety previously evaluated in the FSARU?
  5. Create the possibility of an accident of a type different from any previously evaluated in the FSARU?
  6. Create the possibility of a malfunction of an SSC important to safety with a result different from any previously evaluated in the FSARU?
  7. Result in a design basis limit for a fission product barrier as described in the FSARU being exceeded or altered?
  8. Result in a departure from a method of evaluation described in the FSARU used in establishing the design bases or in the safety analyses?

The Bechtel report continues:“Consequently, subject to the limitations of the Phase 2 assessment information, implementation of the closed cooling technology, the inshore dual-flow fine mesh screens, or the offshore modular wedge wire screening system design alternatives is believed to not require a License Amendment Request (LAR) in accordance with 10 CFR 50.59.”

Among the crucial words in these two quotes are the “Conditional words,” as follows: “the anticipated responses … would be NO” [first sentence in the above quote], and “subject to the limitations of the Phase 2 assessment information, implementation [of any of the options] is believed not to require a License Amendment Request” [final sentence in the above quote.]

Bechtel’s conclusion concerning safety and DCISC’s evaluation of it

We understand Bechtel’s conclusion to mean the following: Although more information would be needed to support a definitive conclusion, Bechtel, applying its expert judgment and based on the information at hand, concludes that any of the proposed cooling options can be implemented in a way that will meet NRC requirements vis-à-vis nuclear-reactor-safety. In fact, Bechtel’s conclusion is stronger than that. Bechtel’s judgment is that it is likely that for any of the seven cooling options under consideration, the nuclear-reactor-safety impact on the plant would be modest enough that PG&E would not even need to request a NRC license amendment request (LAR) before it could proceed with installing that option at Diablo Canyon. (All of this is subject to Bechtel’s appropriate caveat that more detailed information will ultimately be needed, as the specific design details are developed, before a sufficient basis will be available for a firmer judgment.)

The DCISC has reviewed Bechtel’s conclusion and the basis for it. We believe that not enough information is available now to conclude definitively that any of the seven options will meet NRC’s nuclear-reactor-safety regulations. That will need to await specific design details that are not available now.

We conclude that the Bechtel assessment that no LAR is required might be correct for the inshore fine-mesh screening system option, because this option involves the least extensive modifications to the plant; however, this assessment is questionable for the off-shore, modular wedge-wire system, because this option requires the installation of a new, safety-related stop-log system in the plant intake cove. The addition of a new, safety-related system will certainly require a NRC LAR.

We conclude that the Bechtel assessment is likely to be incorrect for the various closed-cycle cooling options. All of these options involve very extensive modifications to the plant, including modifications to the plant intake structure that also houses the ASW system, protected area boundary, turbine building (which houses safety-related emergency diesel generators and electrical switchgear), and rerouting of the plant’s 230-kV alternate offsite power transmission system. These major modifications have the potential to affect the operability of safety-related systems both during and following construction, and potential undesirable interactions will require detailed design review by the NRC to identify and mitigate.

While we conclude that most of the proposed cooling system modifications would require a NRC license amendment request, Bechtel’s conceptual design study has sufficient detail to allow a preliminary conclusion that NRC approval of the license amendment could likely be obtained. The most important bases for this, in our view, are two:

  1. First, Bechtel has performed a set of nuclear-reactor-safety evaluations against each of the various 10 CFR 50.59 criteria for each of the seven alternative cooling technologies.
  2. Second, around the world there are a wide variety of cooling designs deployed today at the few hundred operating nuclear power plants. The seven options under consideration here are each represented (broadly, although not in technical detail) elsewhere, and at large numbers of plants for the closed-cycle options. Less experience exists with intake fine screening and offshore modular wedge-wire systems under conditions relevant to the Diablo Canyon site, and we therefore believe that a testing program should be conducted or actual experience elsewhere reviewed to verify performance of either system before it should be selected. Furthermore, for any of the seven proposed alternatives, there is the potential for a significant reduction in the plant’s reliability and for an increase in the frequency of trips and forced outages. Much additional work would be needed before assurances could be had that the overall safety impact of these potential issues is manageable. However, because these cooling technologies exist, can be and have been designed and operated safely elsewhere, we judge that it is probably feasible to deploy any of these seven options at Diablo Canyon in a manner that will meet NRC safety regulations.

However, this finding on our part is not sufficient for us. That is, the DCISC has developed a different criterion for judging the safety of an alternative cooling technology at Diablo Canyon. The next section will explain why we have a different criterion, after which we will present our safety criterion and our evaluation based on it.

The ultimate heat sink

The preceding discussion covered the normal non-safety-related plant cooling system, which discharges waste heat from the condenser to the Pacific Ocean via a Once-Through Cooling System. A totally separate system, the nuclear-safety-related Auxiliary Saltwater System, discharges plant decay heat to the Pacific Ocean in certain shutdown, off-normal, and emergency conditions. This arrangement is called the Ultimate Heat Sink (UHS) because it is the final or ultimate opportunity to keep the plant cool and safe if all other methods are unavailable or have failed.

With two exceptions the seven cooling alternatives proposed by Bechtel would be independent and separate from the UHS, and thus should normally have no adverse impact on nuclear-reactor safety from the UHS standpoint. The two exceptions are the following options:

We are also concerned about a third issue:

The first two alternative cooling options both utilize the current OTC intake cove and intake structure, which also house the ASW System, part of the UHS. At this stage it appears that these two options would affect the UHS, but final design and analysis would be necessary to permit a determination of the significance. The third item, construction/installation, could adversely impact ASW/UHS, which concerns the DCISC at this conceptual stage. We believe that compensatory measures would likely be taken; however, we reserve final judgment until more is known about this impact.

The DCISC has been studying this issue since December 2010, and in its most recent 2010–2011 Annual Report (Reference 11), it concluded the following:

“A range of adverse nuclear safety impacts is known qualitatively at this time and is of concern to the DCISC. The DCISC will continue to take seriously the charge to review the safety impacts of the elimination of Once Through Cooling (OTC) at DCPP and provide analysis and input to the process.”

Bechtel concluded the following:

“The safety-related ASW system is not affected by this modification. The CWS (Circulating Water System)and the SCW (Service Cooling Water)system do not provide cooling to any component required for safe shutdown. The CW (Circulating Water)pumps are not required for the safety of the units. A complete shutdown of the SCW system would not affect safe shutdown of the reactor. The replacement of the once-through cooling with closed cycle cooling would result in an increase in circulating water temperature. This increase is not expected to adversely affect FSARU accident analyses since these systems serve no safety related functions.”

The DCISC agrees that the alternative cooling systems would not adversely affect the FSARU accident analyses provided that the ASW/UHS is not affected by the proposed alternative cooling system, which appears to be the case based on Bechtel’s conceptual studies performed to date, but the reliability of this non-safety related equipment may affect the frequency of plant trips and equipment failures that require safety-related equipment to function in order to prevent or mitigate accidents. Insufficient information is available to answer the question of whether the alternative cooling systems might affect the frequency of accident initiating events.

Effects of plant modifications on plant reliability

One of DCISC’s principal concerns with the proposed alternative cooling options is their potential impact on the plant’s reliability, and the potential to increase the frequency of plant trips and forced outages that stress plant safety systems (e.g., ASW/UHS) and can provide initiators for accidents. Much of the improvement in nuclear plant safety around the world in the last three decades has come from improved operational methods that have greatly reduced the frequency of plant trips and forced outages.

While the DCISC assesses that the proposed alternative cooling methods could be successfully licensed by the NRC, the level of design detail and information is insufficient to assess the likely affects of the design changes on plant reliability. For example, the closed-cycle options all involve a substantial increase in the operating pressure of the circulating water system, and the potential for increased flooding risk can only be assessed following detailed design. Likewise, the wet closed cycle options include a water storage capacity of only two hours (Reference 2, Section 4.3.4.1) so any outage of the water supply system exceeding this will result in a plant trip. For all systems, there will be a learning curve associated with the transition to alternative cooling that will result in increased risk of plant trips during the learning period.

The importance of the ultimate heat sink in reactor safety, and how an understanding of this importance is developed

Before describing the nuclear-reactor-safety criterion that the DCISC has used in this evaluation, we need to explain something about nuclear-power-plant risk, and about how it is understood by the community of nuclear-power-plant safety analysts.

Every operating US nuclear power reactor, including the two units at Diablo Canyon, meets all applicable NRC regulations. (Otherwise, it would not be operating.) However, this does not mean that any of these reactors presents zero risk to the public. While the NRC has judged the risks acceptably low, the possibility of a release of radioactivity that might affect the public does exist. We will call the ensemble of these risks of a radioactive release the “residual risk,” the word “residual” meaning to imply that these are the risks that remain after all of the hard work has been done to reduce the risks to low levels that are acceptable to the NRC and to the DCISC.

Reactor safety analysts study these risks using many different approaches. The approach that provides the most realistic understanding is embodied in an analysis technology known as “probabilistic risk assessment” (PRA), which delineates every important “accident sequence” that might arise at a given reactor. In the PRA, each such accident sequence begins with a specified “Initiating event” (such as an equipment failure, a human error, an electrical fire, or an event external to the plant like an earthquake), proceeds through a series of other failures (either equipment failures or operator errors), and ends up with an end-state other than a “safe, stable” end state. (A PRA sequence that ends up at a “safe, stable” end-state is not an “accident.”) For those sequences that do not end “safe and stable,” the PRA evaluates the overall annual probability of occurrence, the sequence of events that would take place, and the consequences were the sequence to occur. The consequences are analyzed and described quantitatively in terms of damage to the reactor core, the potential for releases of radioactivity from the core to the building, the physical, chemical, and radiological character of those releases, and ultimately the possible release of radioactivity to the environment outside the plant.

It is important to note that the initiating events that can lead to accidents do not necessarily involve safety related systems. Instead, as the reactor-safety community knows from both analysis and operating experience, sometimes these accident sequences may initially involve failures of non-safety related equipment, which then require that safety-related systems function in order to prevent or mitigate an accident. Thus data for the reliability of non-safety-related equipment and systems is a key input to PRA assessments, in addition to that for safety-related systems.

The Diablo Canyon station has performed a PRA of good quality (Reference 5), which is used essentially every day to help understand various issues at the plant as they arise. This PRA is currently being updated in important ways, a process that goes on periodically at Diablo Canyon as elsewhere around the country, because new PRA methodologies are continually being developed, data bases for equipment failures and the like are continually being revised with new information, and there is now a methodology standard for PRA (Reference 6) that is used throughout the U.S. to which the Diablo Canyon PRA is being compared.

The DCISC has reviewed the Diablo Canyon PRA, and also studied several later reviews of it by others (References 7, 8, and 9). We judge that the residual risk as described in the PRA is acceptably small, and have used that judgment as one basis for our conclusion that the plant’s two reactors are now being operated safely.

As noted, many different types of accident sequences can occur at Diablo Canyon, and the PRA analyzes them. Among these accident sequences are some that involve prolonged loss of the function of discharging the waste heat to the environment. Prolonged loss of this function can lead to a serious accident, which is why great care is taken at every nuclear plant in the design and operation of the equipment and structures that carry out this function. There are potential sequences in which loss of this function is the initiating event, and others in which this function is lost as a consequence of another initiating event, such as an equipment failure elsewhere in the plant.

The DCISC has reached two important conclusions about Diablo Canyon that need to be understood before we can explain our evaluation here. First, the DCISC judges (as noted above and based in part on the PRA) that the current level of safety achieved at Diablo Canyon is acceptable. Second, the PRA, which the DCISC judges to be technically sound, finds that none of the major contributors to the residual risk from accident sequences at Diablo Canyon involve prolonged loss of the normal function of discharging the waste heat to the environment.

While prolonged loss of circulating water system (CWS) function is not an important contributor to risk at DCPP with today’s configuration, abrupt loss of CWS results in one of the more severe types of transients the plant can experience. The risk arises from the coupling between different pieces of equipment during the transient, which can affect equipment reliability in ways not fully captured by the normal reliability data. In the case of abrupt failure of CWS, a normal turbine and reactor trip occur, but the capability to dump excess steam to control the primary system pressure and temperature is reduced because the capacity of the turbine condenser to accept steam is lost. Thus abrupt CWS failures result in a larger temperature and pressure transient to the primary system than during normal plant trips. While these temperatures and pressures remain within the design capability of the primary system, the greater stresses increase the probability of failures of safety-related components. For this reason, the DCISC recommends that special attention be paid to assure that any cooling system modifications do not result in a significant reduction in the reliability of the CWS function.

Another consideration is important to mention here. As a result of insights from the Fukushima nuclear-plant accident in Japan in March 2011, the NRC has ordered all US operating reactors to perform certain studies and based on them to carry out certain safety improvements; other safety improvements may be required by the NRC in the future based on technical studies now under way. In parallel, the US nuclear-power-reactor industry as a whole has undertaken other studies, and has taken the initiative to propose a set of safety improvements that it believes are required and beneficial. Among these latter is an industry initiative, known as “FLEX” (Reference 10), that among other benefits will provide each nuclear plant with a more robust capability to respond in the unlikely event of a prolonged loss of ultimate heat sink. We note that the specifics of these FLEX improvements have not yet been finalized, either at Diablo Canyon or anywhere else, but they are surely going to be installed in one form or another, and they will provide Diablo Canyon with an even stronger basis for the safety performance of its current UHS.

The DCISC’s safety criterion

As background, we first reiterate something we noted above, which is that the current OTC approach for providing the normal cooling function at Diablo Canyon meets all applicable NRC requirements. The DCISC is acutely cognizant of the US NRC’s nuclear-reactor-safety criteria for this function, and would not provide a positive evaluation for any technology that did not meet those criteria. However, we have approached our safety evaluation using a different set of criteria. Our position is that, although replacement cooling technology could meet all NRC regulations, it could still represent an unacceptable degradation of the overall nuclear-reactor-safety performance at Diablo Canyon when compared to the current configuration. For this reason, the DCISC criterion can be stated as follows:

Having concluded that the current OTC approach for performing the normal plant cooling function at Diablo Canyon has adequate safety, the DCISC’s safety criterion is that any alternative proposed as a replacement should provide at least approximately the same level of overall nuclear-reactor safety.

In the DCISC’s view, this mainly (but not entirely) comes down to asking the following question of any technology that might be proposed to replace once-through cooling to perform the normal cooling function at Diablo Canyon, after stipulating that the technology must also meet all applicable NRC regulations:

As analyzed in the plant PRA, will the contribution of accident sequences involving loss of cooling remain as only a modest contributor to the total residual risk at Diablo Canyon?1

The DCISC cannot answer this question today, because the analysis has not been performed. However, the DCISC is willing to offer the following assessment: Based on our review of the technical information in front of us, meaning the information in the two Bechtel reports (supplemented by our knowledge of how various cooling technologies perform at other nuclear power plants around the world),we judge it likely that none of the proposed new technologies would pose a significant safety problem at Diablo Canyon, if they do not degrade significantly the plant’s reliability and increase the frequency of plant trips. However, this is not a strong conclusion based on evidence, but merely a judgment based on what we know so far. Crucially, more analysis is needed. Any new technology must be designed, installed, and operated to high reliability standards, and the first step would be the design step, where details must be developed that will lead to an acceptable design solution.

To summarize: While the DCISC has a technical basis for optimism, we cannot determine from the available conceptual information whether any of the proposed alternative technologies will contribute more to the overall plant risk profile at Diablo Canyon than the modest contribution made today by the current cooling technology (using once-through cooling)–and we believe that nobody else can fully determine this yet either.

Summary of DCISC findings and conclusions

DCISC follow-on activities

These are all interim DCISC findings and conclusions, in the sense that as new information is developed (and it will be) any of them is subject to updated evaluation. In particular, as a follow-on to the work done so far on this set of issues, we will undertake the following:

All of the above would be a part of our normal DCISC scope to review operational safety at Diablo Canyon, but because of the special inquiry made by the California SWRCB, we will be especially alert about these issues.

References

  1. Bechtel Power Corporation, “Independent Third-Party Interim Technical Assessment for the Alternative Cooling Technologies or Modifications to the Existing Once-Through Cooling System for Diablo Canyon Power Plant,” Report No. 25762-000-30R-G01G-00009 (November 2012)
  2. Bechtel Power Corporation, “Alternative Cooling Technologies or Modifications to the Existing Once-Through Cooling System for the Diablo Canyon Power Plant,” Report No. 25762-000-30R-G01G-00010 (August 2013)
  3. U.S. Nuclear Regulatory Commission, Title 10 Code of Federal Regulations Part 50.59, “Changes, Tests, and Experiments” (64 Federal Register (FR) 53613, Oct. 4, 1999, as amended at 66 FR 64738, Dec. 14, 2001; 72 FR 49500, Aug. 28, 2007)
  4. Pacific Gas and Electric Company, “Diablo Canyon Power Plant Unit 1 and 2 Final Safety Analysis Report Update” (revised by the plant on a continuing basis; part of the NRC docket for DCPP)
  5. Pacific Gas and Electric Company, “Long Term Seismic Program Final Report,” submitted to the NRC in Dockets No. 50-275 and 50-323 (31 July 1988)
  6. American Society of Mechanical Engineers (ASME) and American Nuclear Society (ANS), “ASME-ANS RA-Sa-2009, Addendum A to RA-S-2008, “standard for Level 1-Large Early Release Frequency Probabilistic Risk Assessment for Nuclear Power Plant Applications” (2009). A new “Addendum B” to this standard is in the final stages of editing now and will be published in late 2013.
  7. Brookhaven National Laboratory, “Review of the Diablo Canyon Probabilistic Risk Assessment,” NUREG/CR-5726, prepared for the U.S. Nuclear Regulatory Commission (1994)
  8. U.S. Nuclear Regulatory Commission, “Individual Plant Examination Program: Perspectives on Reactor Safety and Plant Performance,” Report NUREG-1560 (1977)
  9. U.S. Nuclear Regulatory Commission, “Perspectives Gained from the Individual Plant Examination of External Events (IPEEE) Program,” Report NUREG-1742 (2002)
  10. Nuclear Energy Institute, “Diverse and Flexible Coping Strategies (FLEX) Implementation Guide,” Report No. NEI 12-06, Washington DC (August 2012)
  11. “Diablo Canyon Independent Safety Committee Twenty First Annual Report on the Safety of Diablo Canyon Nuclear Power Plant Operations, July 1, 2010—June 30, 2011”, Approved October 11, 2011, Volume II, Exhibit D.7, Section 3.1, “EPA Closed Cooling.”